Electrical Requirements
|
Shock Hazard
|
|
(FOR EQUIPMENT WITH CE MARK ONLY!) To prevent electric shock hazard this appliance must be bonded to other appliances or touchable metal surfaces in close proximity to this appliance with an equipotential bonding conductor. This appliance is equipped with an equipotential lug for this purpose. The equipotential lug is marked with the following symbol. Equipotential Ground Symbol = |
|
DRYWALL CONSTRUCTION |
Secure unit to building stud approximately six inches either side of service connection. Use cable restraint that is at least six inches short than flexible conduit. |
|
NOTICE - |
It is recommended that a 30 mA rated protective device such as a residual current circuit breaker (RCCB), or ground fault circuit interrupter (GFCI), be used on the circuit.
|
|
NOTICE - |
CE marked fryers require a flexible power cord to be HO7RN type. Additionally, cords used on CE marked fryers must meet the following minimum wire size requirements (taking into account length of cord): 2.5 mm2 (up to 25 Amps), 4 mm2 (up to 32A), 6 mm2 (up to 40A). |
The fryer is supplied with a 7 ft. (2.13 m) power cord assemby:
|
The other power cord, supplying power to the heating system, uses 3NG heating power plug, and each vat has its own power cord assembly. |