Electrical Requirements
Shock Hazard
|
(FOR EQUIPMENT WITH CE MARK ONLY!) To prevent electric shock hazard this appliance must be bonded to other appliances or touchable metal surfaces in close proximity to this appliance with an equipotential bonding conductor. This appliance is equipped with an equipotential lug for this purpose. The equipotential lug is marked with the following symbol. Equipotential Ground Symbol = |
CE units require a minimum wire size of 6 mm to be wired to the terminal block. If a flexible power cord is used, it must be HO7RN type.
NOTICE - | It is recommended that a 30 mA rated protective device such as a residual current circuit breaker (RCCB), or ground fault circuit interrupter (GFCI), be used on the circuit. |
Cable Restraint
Secure I-bolt to building using acceptable building construction practices.
Permanently connected electric fryers with casters must be installed with flexible conduit and a cable restraint, when installed in the United States and internationally. Holes are available in the rear fryer frame for securing the cable restraint to the fryer. The cable restraint does not prevent the fryer from tipping.
DRYWALL CONSTRUCTION | Secure unit to building stud approximately six inches either side of service connection. Use cable restraint that is at least six inches short than flexible conduit. |