HHC 903-10 and SHC 10 CDT Control Special Programming
-
Turn power switch OFF and press and hold the Program button until “SP" displays, followed by the software version.
-
Press the Program button when “°F” or “°C” displays, use the Up and Down arrow buttons to toggle the temperature reading from Fahrenheit to Celsius.
-
Press and release the Program button and “int” displays.
-
Press and hold the Up or Down arrow buttons and display counts down, “in-3, in-2, in-1”. When “int SYS” displays, release the Up or Down arrow button and the initialization is complete. The temperature and timers are now programmed to factory presets.
-
Press and release the Program button and “CAL” displays, followed by the probe temperature, inside the unit.
-
Use the Up and Down arrow buttons to set the displayed temperature to match the actual temperature inside the unit.
-
Press and release the Program button twice and “P= L or U” displays. “P=L” means Locked and the setpoint temperature and timers CANNOT be programmed. “P=U” means Unlocked and the setpoint temperature and timers CAN be programmed. Use the Up and Down arrow buttons to toggle the display from “P=L” to “P=U”.
-
Press and release the Program button and “OP” displays. Use the Up and Down arrow buttons to toggle the outputs ON & OFF. When the outputs are ON, the HEAT ON LED should come on and “8888” displays, indicating the outputs are working correctly.
-
Press and hold the Program button to exit Special Program Mode and all modes will now be set.