Electrical Requirements
208 VAC, 60 Hz, 3 PH, 39.4 A
240 VAC, 50 Hz, 1 PH, 7 A
|
Shock Hazard
|
(FOR EQUIPMENT WITH CE MARK ONLY!) To prevent electric shock hazard this appliance must be bonded to other appliances or touchable metal surfaces in close proximity to this appliance with an equipotential bonding conductor. This appliance is equipped with an equipotential lug for this purpose. The equipotential lug is marked with the following symbol. Equipotential Ground Symbol = |
An all pole, separate disconnect switch, with proper capacity fuses or breakers must be installed at a convenient location between the fryer and the power source, and must be installed according to national and local codes. It should be an insulated copper conductor rated for 600 volts and 90° C. For runs longer than 50 feet (15.24 m), use the next larger wire size. CE units require a minimum wire size of 6 mm to be wired to the terminal block.
NOTICE - |
It is recommended that a 30 mA rated protective device such as a residual current circuit breaker (RCCB), or ground fault circuit interrupter (GFCI), be used on the circuit.
|
Cable Restraint
For Australia or New Zealand Only: Where a model is supplied with castors and is to be connected to a fixed gas supply via a flexible hose connection, a restraining chain or wire of adequate strength shall be fixed to the appliance and be suitable to be fixed to the wall within 50 mm of each connection point. The length of the chain or wire shall not exceed 80% of the length of the hose assembly.
Secure I-bolt to building using acceptable building construction practices.
Permanently connected electric fryers with casters must be installed with flexible conduit and a cable restraint, when installed in the United States and internationally. Holes are available in the rear fryer frame for securing the cable restraint to the fryer. The cable restraint does not prevent the fryer from tipping.
Ensure the cable restraint on moveable gas fryers is installed as shown.
The flexible gas hose cannot exceed 2M in length.
DRYWALL CONSTRUCTION |
Secure unit to building stud approximately six inches either side of service connection. Use cable restraint that is at least six inches short than flexible conduit. |
Each vat has it’s own power cord assembly, and uses the choices of plugs below, depending upon voltage option and location of fryer.
HP Part no: 16242 Hubbell no: HBL8451C Plug 250V/NEMA 15-50P |
HP Part no: 37514 Hubbell no: HBL8461C Plug 250V/NEMA 15-60P |
HP Part no: 21335 Hubbell Part no: HBL8452C Plug 250V/NEMA 15-50P/Angle |
HP Part no: 58146 Hubbell Part no: HBL8462C Plug 250V/NEMA 15-60P/Angle |